HART transparent driver

Model : PR 9107B

Isolated barrier and HART transparent driver for harsh and hazardous environments

  • 24 VDC supply via power rail or connectors
  • Fast response time
  • High active output load 725 Ohm / 20 mA
  • Output line fault detection via status relay
  • Loop break and sensor error detection
  • 2.6kVAC galvanic isolation
  • SIL2 certified via Full Assessment according to IEC 61508

 238 Get an Offer

Clear
Specifications
Accuracy

≤ ±16 μA

Brand

PR Electronics

Certification

ATEX, CCC, DNV, EAC Ex, FM, IECEx, INMETRO, SIL2 Full Assessment IEC 61508, UL

Dimension

109×23.5×104 mm

Function

Isolated Barrier, Signal Driver, Signal Isolator

Input Type

DC Current

Isolation Voltage

2.6 kVAC

Number of Inputs

1, 2

Number of Outputs

1, 2

Output Type

DC Current

Power Supply

20…30 VDC

Programming

4500 series devices

Temperature Coefficient

< ±0.01% of span /°C

Other product features
Channels

1ch, 2ch

Application

  • 9107B is a 1- or 2-channel isolated 1:1 driver barrier for intrinsic safety applications.
  • Operation and drive control of I/P converters, valves and indicators mounted in the hazardous area.
  • Operation of HART devices is possible as the unit transmits HART communication signals bi-directionally.
  • 9107B can be mounted in the safe area or in zone 2 / Cl. 1, div. 2 and transmit signals to zone 0, 1, 2 and zone 20, 21, 22 including mining / Class I/II/III, Div. 1, Gr. A-G.
  • The PR 45xx displays the process value for each channel and can be used to define high and low limits for detection of loop current level. If these limits are exceeded, the status relay will activate.
  • Dual channel versions can be used for signal splitter applications – 1 in and 2 out.

Advanced features

  • The PR 45xx detachable display and the green and red front LEDs indicate operation status for each channel.
  • A tag number can be defined for each channel.
  • Output line fault detection.
  • In the 1-channel version the status relay can be used as a simple limit switch.
  • Suitable for the use in systems up to Performance Level “d” according to ISO-13849.

Technical characteristics

  • High galvanic isolation of 2.6 kVAC.
  • High accuracy better than 0.1%.
  • Continuous check of vital stored data for safety reasons.

Mounting

  • The devices can be mounted vertically or horizontally without distance between neighbouring units.